§ 8-220 — Section 903.2.7 amended
Code of Ordinances of the City of Lawrence, Kansas (Codified through Ordinance No. 10209, enacted April 14, 2026 (Supp. No. 4)) · Lawrence Code of Ordinances § 8-220
Corpus is an independent public-information project, not the official City of Lawrence website. Stable reference: corpuslaw.us/code/ed8f9f53-2833-4f57-8b63-99a9402b1c44
Sec. 8-220. - Section 903.2.7 amended.
Section 903.2.7 of the 2018 International Fire Code is hereby amended to read as follows: 903.2.7. Group M. An automatic sprinkler system shall be provided throughout buildings containing Group M occupancy where one of the following conditions exists: (1) A Group M fire area exceeds 12,000 square feet (1,115 mA2). (2) A Group M fire area is located more than three stories above grade plane. (3) The combined area of all Group M fire areas on all floor, including any mezzanines, exceeds 24,000 square feet (2,230 mA2). (4) A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeding 2,500 square feet (2,230 mA2).
(Code 2018, § 8-221)
Ask a question about Lawrence law
Corpus searches the Lawrence sections it holds and shows the ones that match, with their citations. Free, no sign-in.
