Sec. 8-220. - Section 903.2.7 amended.

Section 903.2.7 of the 2018 International Fire Code is hereby amended to read as follows: 903.2.7. Group M. An automatic sprinkler system shall be provided throughout buildings containing Group M occupancy where one of the following conditions exists: (1) A Group M fire area exceeds 12,000 square feet (1,115 mA2). (2) A Group M fire area is located more than three stories above grade plane. (3) The combined area of all Group M fire areas on all floor, including any mezzanines, exceeds 24,000 square feet (2,230 mA2). (4) A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeding 2,500 square feet (2,230 mA2).

(Code 2018, § 8-221)