Sec. 8-150. - Tests.
(a) All original installations, and where practical all extensions and alterations to gas piping, must be tested with a mercury gauge or an air gauge, and must be capable of withstanding a pressure of 60 pounds per square inch on the main line to the meter and 20 pounds per square inch on the meter to the appliance for a period of 15 minutes without loss. The test is to be made before the appliances are hung. All gauges must be set as required. (b) If, upon inspection and test, the installation of any gas piping or any part thereof shall be found not to comply with the requirements of this article, the same shall be changed, rearranged, repaired or removed, and the gas shall not be permitted to flow through any piping until the same has been inspected and approved by the building official.
(Code 1973, §§ 4-413, 4-414; Ord. No. 4017, § 3, 12-7-82)