Section 507.5 of the International Fire Code is hereby amended to read as follows: 507.5 Fire hydrant systems. Fire hydrant systems shall comply with Sections 507.5.1 through 507.5.6. 507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 feet (122 m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Exceptions: (1) 1. For Group R-3 occupancies, the distance shall be 600 feet (183 m). (2) 2. For agricultural structures classified as Group U occupancies, the distance shall be 600 feet (183 m) or as approved by the fire code official. 507.5.1.1 Hydrant for standpipe systems. Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet (30 480 mm) of the fire department connections. Exception: The distance shall be permitted to exceed 100 feet (30 480 mm) where approved by the fire code official. 507.5.2 Inspection, testing and maintenance. Fire hydrant systems shall be subject to periodic tests as required by the fire code official. Fire hydrant systems shall be maintained in an operative condition at all times and shall be repaired where defective. Additions, repairs, alterations and servicing shall comply with approved standards. 507.5.3 Private fire service mains and water tanks. Private hydrants shall be painted red in color. Private fire service mains and water tanks shall be periodically inspected, tested and maintained in accordance with NFPA 25 at the following intervals: (1) 1. Private fire hydrants of all types: Inspection annually and after each operation; flow test and maintenance annually. (2) 2. Fire service main piping: Inspection of exposed, annually; flow test every 5 years. (3) 3. Fire service main piping strainers: Inspection and maintenance after each use. 507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all times. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. All hydrants shall be painted and highly visible. 507.5.5 Clear space around hydrants. A 3-foot (914 mm) clear space shall be maintained around the circumference of fire hydrants, except as otherwise required or approved. 507.5.6 Physical protection. Where fire hydrants are subject to impact by a motor vehicle, guard posts or other approved means shall comply with Section 312. (History: Ord. No. BC-3499, §87, 2026; Ord. No. BC-3286 §118, 2020; Ord. No. BC-2936 §87, 2012) Effective on: 1/1/1901

Ask a question about Overland Park law

Corpus searches the Overland Park sections it holds and shows the ones that match, with their citations. Free, no sign-in.