§ 16.360.210.52 — (C)(3)

Code of the City of Overland Park, Kansas · Overland Park Municipal Code, tit. 16, art. 16.360, § 16.360.210.52

Corpus is an independent public-information project, not the official City of Overland Park website. Stable reference: corpuslaw.us/code/9be782cb-f3d3-4bc6-ae5e-5ee378d8889f

16.360.210.52(C)(3)

Article 210, Section 210.52(C)(3) of the National Electrical Code is hereby amended to read as follows: 210.52(C)(3) Receptacle Outlet Location. Receptacle outlets shall be located in one or more of the following: (1) 1. On or above, but not more than 20 inches above, the countertop or work surface. (2) 2. In countertop or work surfaces: Receptacle outlet assemblies listed for use in the countertops or work surfaces shall be permitted to be installed in countertops or work surfaces. (3) 3. Below countertop or work surfaces: Not more than 12 inches below the countertop or work surface. Receptacles installed below a countertop or work surface shall not be located where the countertop or work surface extends more than 6 inches beyond its support base. (History: Ord. No. BC-3499, 1§59, 2026) Effective on: 1/1/1901