§ 8-1-5-210.8(A) — Amendment to Article 210.8(A) of the NEC

Salina Code, City of Salina, Kansas (Codified through Ordinance No. 26-11299 adopted August 24, 2026. (Supp. No. 19)) · Salina Municipal Code § 8-1-5-210.8(A)

Corpus is an independent public-information project, not the official City of Salina website. Stable reference: corpuslaw.us/code/f8b0898e-c88f-4601-b8ab-3245f0737c6e

Sec. 8-1-5-210.8(A). - Amendment to Article 210.8(A) of the NEC.

Section 210.8(A) of the NEC is amended to read as follows: Sec. 210.8(A) Dwelling Units. All 125-volt, single-phase, 15- and 20- ampere receptacles installed in the locations specified in 210.8(A)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms. (2) Garages, and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use. (3) Outdoors. Exception to (3): Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable. (4) Crawl spaces - at or below grade level. (5) Unfinished portions or areas of the basement not intended as habitable rooms. Exception to (5): A receptacle supplying only a permanently installed fire alarm or burglar alarm system shall not be required to have ground-fault circuit-interrupter protection. (6) Kitchens - where the receptacles are installed to serve the countertop surfaces. (7) Sinks - where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink. (8) Boathouses. (9) Bathtubs or shower stalls - where receptacles are installed within 1.8 m (6 ft) of the outside edge of the bathtub or shower stall. (10) Laundry areas. Exception to (2-10): Any appliance that is directly wired without the use of receptacle, or the appliance receptacle serving said appliance is not readily accessible, shall not be required to have ground fault circuit interrupter protection. Any appliance serving sanitary or emergency use, such as sewer ejection pumps and sump pumps, shall not be required to have ground fault circuit interrupter protection.

(Ord. No. 25-11268, § 1, 12-8-25)

Ask a question about Salina law

Corpus searches the Salina sections it holds and shows the ones that match, with their citations. Free, no sign-in.