§ 15.08.020 — Amendments and Additions

Municipal Code of the City of Shawnee, Kansas (Codified through Ordinance No. 3558, adopted August 10, 2026. (Supp. No. 9, Update 2)) · Shawnee Municipal Code § 15.08.020

Corpus is an independent public-information project, not the official City of Shawnee website. Stable reference: corpuslaw.us/code/79fd2a2f-b2a2-409b-a184-6d6788caf078

15.08.020 - Amendments and Additions.

The following sections of the NEC, as adopted by Section 15.08.010, are amended as follows: A. 90.1(D) Administration and Enforcement. The administrative provisions of the 2024 International Building Code, Chapter 1, in its entirety, and as modified by the Shawnee Municipal Code, shall govern all matters within the scope of the NEC. B. Amend by omitting Section 210.50(C)(3) Receptacle Outlet Location., of the NEC, and amend by adding a new Section 210.50(C)(3) Receptacle Outlet Location., which reads: 210.50(C)(3) Receptacle outlet location. Receptacle outlets shall be located in one or more of the following: 1. On or above, but not more than 20 inches (508 mm) above, the countertop or work surface. 2. Receptacle outlet assemblies listed for the use in countertops or work surfaces shall be permitted to be installed in countertops or work surfaces. 3. Not more than 12 inches (305 mm) below the countertop or work surface. Receptacles installed below a countertop or work surface shall not be located where the countertop or work surface extends more than 6 inches (152 mm) beyond its support base. C. Amend by omitting Section 625.43 Disconnection Means., of the NEC, and amend by adding a new Section 625.43 Disconnection Means., which reads: 625.43 Disconnection means. Electrical Vehicle Charging Station (EVCS) and Wireless Power Transfer Equipment (WPTE) shall be provided with one or more disconnecting means in accordance with 625.43(A) and 625.43(B). 625.43 (A) Equipment Disconnects. For fixed in place EVCS and WPTE rated more than 150 volts to ground, the disconnecting means shall be provided and installed in a readily accessible location. If the disconnecting means is installed remote from the equipment, a plaque shall be installed on the equipment denoting the location of the disconnecting means. The disconnect shall be lockable in accordance with Section 110.25. 625.44 (B) Emergency Shutoff. For fixed-in-place equipment supplying DC power to the vehicle, one or more clearly identified emergency shutoff devices or electrical disconnects shall be provided and shall meet the following: (1) Be installed in a readily accessible location in sight of the equipment and located not less than 20 ft and no more 100 ft from the equipment. (2) Disconnect power to all electric vehicle power transfer equipment collocated. (3) Be clearly marked "ELECTRIC VEHICLE EMERGENCY DISCONNECT." (4) Require manual reset of the emergency shutoff condition. (5) Disconnect all ungrounded conductors simultaneously from the source of supply. The disconnecting means required in accordance with 625.43(A) shall be permitted to serve as the emergency disconnect if it complies with all requirements of 625.43(B).

(Ord. No. 3536, 2025)

Ask a question about Shawnee law

Corpus searches the Shawnee sections it holds and shows the ones that match, with their citations. Free, no sign-in.