Sec. 15.02.030. - Required alarm location.

A. In dwellings, smoke alarms shall be mounted on the ceiling or wall at a point centrally located in the corridor or area giving access to each separate sleeping area. Where bedrooms are on an upper level, the alarm shall be placed directly above the stairway. In dwellings with split levels, an alarm need only be installed on the upper level provided the lower level is less than one full story below the upper level, except that if there is a door between levels an alarm is required to be installed on each level. Dwellings having a stairway which opens from the basement shall have an alarm installed in the basement. Such alarm shall be connected to a sounding device or other alarm to provide an alarm which will be audible in all sleeping areas. B. In hotels, motels, or lodging houses, alarms shall be located on the ceiling or wall of each guest room. When guest rooms are on an upper level, the alarm shall be placed on the ceiling of the upper level in close proximity to the stairway. C. When activated, required alarms shall provide an alarm which shall be clearly audible in all sleeping areas over background noise levels with all intervening doors closed. D. A smoke alarm mounted on a wall shall not be mounted more than twelve inches below the ceiling or closer than four inches to the ceiling. A smoke alarm mounted on the ceiling shall not be closer than four inches from the wall. E. Smoke alarms located in rooms with ceiling slopes greater than one foot rise per eight feet horizontally shall be located at the high side of the room. F. Smoke alarms installed at the head of the stairway shall be so located as to assure that smoke rising in the stairwell cannot be prevented from reaching the alarm by an intervening door or obstruction. G. In dwelling units where the ceiling height of a room open to the hallway serving the bedrooms exceeds that of the hallway by twenty-four inches or more, smoke alarms shall be installed in the hallway and in the adjacent room.

(Ord. No. 48-893, § 3, 11-9-2010)

Ask a question about Wichita law

Corpus searches the Wichita sections it holds and shows the ones that match, with their citations. Free, no sign-in.