Sec. 114-74. - Required backflow prevention assemblies or methods for containment.
(a) Water service assemblies: An air gap or an approved reduced pressure principle backflow prevention assembly is required for water services having one or more potential cross-connections which the administrative authority classifies as high hazard as defined by tables D104 and D105. (b) Fire protection system assemblies: (1) All proposed installations of fire suppression systems shall be reviewed by the chief plumbing inspector to determine the appropriate type of backflow prevention devices or methods required. (2) For all proposed fire suppression systems using antifreeze, a reduced pressure principle (#10 on Table D104) backflow prevention device shall be installed at the point of entry. The customer shall provide the city with the design and chemical usage of the fire suppression system. (3) All existing fire suppression systems shall meet the requirements of section 114-74 above. An inspection by a fire suppression specialist shall be done to determine whether antifreeze has been utilized in the suppression system. The inspection shall be done at the expense of the customer. If it cannot be certified that antifreeze has been used, then a backflow prevention device shall be installed as prescribed by Table D104 and as approved by the chief plumbing inspector. Installation shall be at the expense of the customer. The required backflow prevention devices or methods shall be installed at the time the system is repaired or changed, or within 12 months after adoption of this division, whichever occurs first. (4) In the event cross-connections, such as those found in using auxiliary water supply systems or in providing other water additives such as foaming agents, are necessary for the proper operation of the fire suppression system, then an air gap or a reduced pressure principle backflow prevention device shall be installed in an approved manner.
(Ord. No. 79-2010, § 9, 8-17-2010)
Ask a question about Bossier City law
Corpus searches the Bossier City sections it holds and shows the ones that match, with their citations. Free, no sign-in.