Sec. 5-110. - Installation of smoke-detecting devices.
Every residential unit of any single or multifamily designation, or rooming house, boarding house, lodging house, hospital, school, day care center or nursery, and other such places where persons may rest or sleep, not necessarily limited to the specific types of structures enumerated in this section, and the units and rooms therein, shall have installed by the owner, smoke-detecting devices. These devices shall be of a type approved by the Underwriters' Laboratories and shall be provided for every eight hundred (800) square feet of living space and any fractional portion thereof exceeding four hundred (400) square feet. Units shall be provided in a location easily accessible to the human ear, in the event of the sounding of the alarm, in relationship to bedroom and other sleeping areas. A building permit shall not be issued for the construction or alteration or repairs of any structure of the aforementioned type, unless the locations of smoke-detecting devices are clearly designated in accordance with this section.
(Ord. No. 8165, 9-2-99)