§ 30-65 — Minimum requirements for private water mains and fire hydrants

Code of Ordinances, City of Shreveport, Louisiana (Supp. No. 85, Update1: codified through Ordinance No.150, 2025 adopted December 9, 2025) · Shreveport City Code § 30-65

Corpus is an independent public-information project, not the official City of Shreveport website. Stable reference: corpuslaw.us/code/c727cf7b-b907-4d50-81e9-237bc00d2072

Sec. 30-65. - Minimum requirements for private water mains and fire hydrants.

(a) All water mains for fire hydrants shall be not less than six inches and shall be of materials approved by the public utilities department. There shall be no dead ends except on water mains eight inches or larger. The length of these dead-ends shall be determined by the fire chief, but dead end eight-inch water mains shall not exceed 1,000 feet. (b) When mains are required to be looped, they may be provided with a UL-listed locking type post indicator and valve at one end of the loop tie-in. The indicator must be kept locked in the closed position with keys issued to the fire department and public utilities department. This valve will not be a part of the meter loop or bypass. However, the minimum fire flow quantities required shall be obtainable without the opening of the post indicator valve. (c) Hydrants shall conform to all city specifications for fire hydrants. Each fire hydrant shall be capable of a minimum water flow of 600 gallons per minute. (d) Fire hydrants shall be located on the private water mains, as required by this article, not more than 400 feet apart unless the fire flow requirements prescribe closer spacing. All buildings with a gross floor area greater than 10,000 square feet shall be within 750 feet of a fire hydrant. The gross floor area shall be within 900 feet of a fire hydrant. Buildings with a gross floor area of 10,000 square feet or less shall be within 900 feet of a hydrant. The gross floor area shall be determined by the chief building official or his designee. (e) When private water mains are laid where there are no structures to be protected, spacing of fire hydrants may be allowed at greater than 400-foot intervals only by approval of the fire chief. (f) All fire hydrants shall be fully accessible to firefighters, fire protection equipment, and for maintenance. Fire hydrants on private mains shall be located within eight feet from an all-weather surface. Variances in the distance from the all-weather surface shall be subject to terms and conditions as stipulated by the fire chief or his designee. (g) All required water mains shall be capable of being flushed periodically as may be prescribed by the public utilities to remove trapped stagnant water or any possible contamination. The public utilities department shall provide such flushing service as may be necessary or required by that department.

(Code 1971, § 15-53)

Ask a question about Shreveport law

Corpus searches the Shreveport sections it holds and shows the ones that match, with their citations. Free, no sign-in.