Sec. 94-64. - Fire line service; fire service storage tanks.

(a) No connection for a sprinkler or fire service shall be permitted unless application therefore has been made to and granted by the department and approved by the chief building official of the city. In no instance shall any connection be made with any sprinkler or fire service without the written consent of the department. Should it be found that any unauthorized connection has been made, or that any water has been used from a sprinkler or fire service for any other purpose than extinguishing a fire, or that a waste of water is permitted from such connection through leaks in the pipes or fixtures, the water service shall be discontinued until a meter of the kind and size prescribed by the director of water and sewerage shall have been installed at the expense of the customer. (b) The furnishing, installation, maintenance and inspection of all meters and services, checks, bypasses, valves, piping, etc., necessary for the installation and operation of sprinkler systems and fire services shall be at the expense of the customer. (c) When ground storage reservoirs or fire pumps are installed on private property, such pumps shall discharge into a fire system approved by the director and the chief building official. An approved backflow preventer shall be installed in the owner's fire service between the point where the pump discharges into such service and the connection of such fire service to the city mains to prevent backflow from the fire pump into the city distribution system. The water in such fire storage tanks will be maintained in a potable condition and subject to periodic inspection by department personnel. Such tanks and water quality shall be maintained in compliance with the standards and requirements of the state department of health and hospitals and the city. Such tanks shall not be of the pressure type. The delivery of city water to the tank shall be above the tank flow line with a one-foot air gap. The supply line to this tank shall not be controlled by a quick-acting valve which will cause water hammer in the distribution system. Water tanks shall be equipped with an overflow pipe at least 12 inches below the city inlet pipe. The overflow pipe shall be protected as to prevent access of insects, birds or animal life into the reservoir. The pipe shall be at least two inches in diameter larger than the inlet supply line from the city distribution system. Such storage tank shall be provided with a drain-pipe and valve for easy drainage of the tank. The drain-pipe may not be connected to the city sanitary sewerage system.

(Ord. No. 112, 1992, § 37-34, 8-11-92; Ord. No. 81, 2003, 7-8-03; Ord. No. 15, 2013, 8-27-13; Ord. No. 109, 2014, 11-11-14)

Ask a question about Shreveport law

Corpus searches the Shreveport sections it holds and shows the ones that match, with their citations. Free, no sign-in.