Sec. 7-405. - Hardening and tempering tanks.
(a) Tanks shall be located as far as possible from furnaces and shall not be located on or near combustible floors. (b) Tanks shall be provided with a noncombustible hood and vent or other equally effective means, venting to outside of building to serve as a vent in case of fire. All such vent ducts shall be treated as flues and be kept well away from combustible roofs or materials. (c) Tanks shall be equipped with a high temperature limit switch arranged to sound an alarm when the temperature of the quenching medium reaches fifty (50) degrees Fahrenheit below the flash point. (d) Hardening and tempering tanks of over five hundred (500) gallons capacity or twenty-five (25) square feet liquid surface area shall be provided with fire-extinguishing equipment. (e) Air under pressure shall not be used to fill or to agitate oil in tanks.
(Code 1965, § 7-173)