Sec. 7-438. - Underground—Installation.
Excavation for underground storage tanks shall be made with due care to avoid undermining of foundations of existing structures. Underground tanks shall be set on firm foundations and surrounded with soft earth or sand well-tamped in place. Tanks shall be covered with a minimum of two (2) feet of earth, or shall be covered with not less than one foot of earth on top of which shall be placed a slab of reinforced concrete not less than four (4) inches thick. When underground tanks are or are likely to be subjected to traffic, they shall be protected against damage from vehicles passing over them by at least three (3) feet of earth cover or eighteen (18) inches of well-tamped earth, plus six (6) inches of reinforced concrete paving is used as part of the protection, it shall extend at least one foot horizontally beyond the outline of the tank in all directions.
(Code 1965, § 7-181)