§ 7-462 — Same—Design and construction of inside storage rooms

Code of Ordinances of the City of Brockton, Massachusetts (Codified through Ordinance No. 07-31-2025(2), approved July 31, 2025 (Supp. No. 28)) · Brockton Code of Ordinances § 7-462

Corpus is an independent public-information project, not the official City of Brockton website. Stable reference: corpuslaw.us/code/9cbfa9f6-0bea-4735-887a-652b28ebb0f1

Sec. 7-462. - Same—Design and construction of inside storage rooms.

(a) Inside storage rooms shall comply with the following general construction requirements: (1) Walls, floors and ceilings shall be of construction having a fire resistance rating of not less than one hour. (2) Openings to other rooms or buildings shall be provided with noncombustible liquid-tight raised sills or ramps at least six (6) inches in height and with approved fire doors arranged to close doors automatically in case of fire. (3) Where other portions of the building or other properties are exposed, windows shall be protected in an approved manner. (4) No combustible material shall be used for interior room surfaces or shelving. (5) Proper ventilation shall be provided. (6) Heating shall be restricted to low pressure steam or hot water or to electrical units approved for Class I hazardous locations. (b) Electrical devices located in inside storage rooms used for Class I flammable liquids shall be approved for Class 1, division 2, hazardous locations; for Class II or III flammable liquids, shall be approved for general use. Installation shall be made in accordance with nationally recognized safe practice. Compliance with the standards of the national board of fire underwriters known as the National Electrical Code shall be deemed prima facie evidence of compliance with nationally recognized safe practice. (c) Rooms or portions of buildings, affording a type of building construction and other features equivalent to that required for inside storage rooms may be utilized for storage of flammable liquids, if not used for any other storage or operation which, in combination, create a great fire hazard. (d) Storage rooms shall be located to minimize damage in the event of an explosion. (e) The quantity of flammable liquid in an inside storage room shall not exceed the quantity specified in this subsection except as provided in subsection (f) of this section. (1) If not protected by an approved automatic fire-extinguishing system, five hundred and fifty (550) gallons total, of which not more than two hundred seventy-five (275) gallons may be of Class I flammable liquid. (2) If protected by an approved automatic fire extinguishing system, one thousand one hundred (1,100) gallons total, of which not more than five hundred fifty (550) gallons may be of Class I flammable liquid. (f) The quantity of flammable liquid in an inside storage room may be increased to that permitted by section 7-468; provided, that the construction is as provided in subsections (a) and (b) of this section, but with walls, ceilings and floors of noncombustible construction having a fire resistance rating of not less than one hour.

(Code 1965, § 7-189)

Ask a question about Brockton law

Corpus searches the Brockton sections it holds and shows the ones that match, with their citations. Free, no sign-in.