§ 7-679 — Ventilation
Code of Ordinances of the City of Brockton, Massachusetts (Codified through Ordinance No. 07-31-2025(2), approved July 31, 2025 (Supp. No. 28)) · Brockton Code of Ordinances § 7-679
Corpus is an independent public-information project, not the official City of Brockton website. Stable reference: corpuslaw.us/code/2d9e761a-ab4d-49a6-8c95-785bed6489ba
Sec. 7-679. - Ventilation.
(a) Ovens in which flammable or toxic vapors are liberated or through which products of combustion are circulated shall be ventilated by the introduction of a supply of fresh air and proper exhaust to outdoors. Discharge pipes shall not terminate within ten (10) feet measured horizontally from any door, window or wood frame walls of any building. Such oven ventilation shall be arranged to provide vigorous and well distributed air circulation within the oven and to insure that the flammable vapor concentration will be safely below the lower explosive limit at all times. Unless the oven is operated in accordance with specific approval specifying particular solvents and rate of ventilation, the rate of ventilations shall not be less than ten thousand (10,000) cubic feet of fresh air per gallon of solvent evaporated in continuous process ovens, and not less than three hundred (300) cubic feet per minute per gallon of flammable solvent evaporated in batch process ovens. (b) Exhaust duct openings shall be located in the area of greatest concentration of vapors. (c) All exhaust shall be by mechanical means using power driven fans.
(Code 1965, § 7-271)
Ask a question about Brockton law