Sec. 7-719. - Refuse chutes.
(a) An automatic sprinkler shall be installed at the top of refuse chutes, and a sprinkler in the bin or room into which the chute discharges. (b) Chutes shall extend to at least four (4) feet above the roof and be covered by a metal skylight glazed with thin plain glass. (c) Chutes shall rest on substantial noncombustible foundations. (d) Walls of chutes shall be clay or shale brickwork at least eight (8) inches thick of reinforced concrete at least six (6) inches thick or equivalent fire resistive construction. (e) Service openings shall be equipped with self-closing fire doors. (f) Each service opening shall be located in a room or compartment cut off from the rest of the floor by a fire partition or firewall from the rest of the building by ceilings or floors. Such walls, ceilings and floors shall have a fire-resistive rating of not less than one hour, and doors to this room or compartment shall be self-closing and have appropriate fire resistance to match the wall construction.
(Code 1965, § 7-291)