§ 902 — Fire Pump and Riser Room Size
Baltimore City Code (current through Ord. 26-129 (July 17, 2026); publication of Oct. 18, 2026) · Baltimore City Code, Building Codes, Part II, Section 902
Corpus is an independent public-information project, not the official City of Baltimore website. Stable reference: corpuslaw.us/code/553574c8-c9d0-4385-bf88-df4d8e069044
Section 902. Fire Pump and Riser Room Size
902.1 Pump and riser room size. 902.1.1 Access. {As in IBC} 902.1.2 Marking on access doors. {As in IBC} 902.1.3 Environment. {As in IBC} 902.1.4 Fire Pump Location. Fire pump and associated equipment shall be located in a separate room that is enclosed with 2-hour fire-resistance-rated fire-separation assemblies. Installation shall comply with requirements of Article 695 of Part III (“Electrical Code”) of this Code.
(Ord. 24-341 Section 1.)