Sec. 7-15. - Amendments to National Electrical Code.
The National Electrical Code, 2020 Edition, is hereby amended in the following respects: (1) Section 110.14. Electrical Connections, Subsection (A). Amend by adding the following: (A) Terminals. "In all cases, copper-clad aluminum wire is prohibited." (2) Section 110.21. Marking. Amend by adding a new paragraph (C). (C) Equipment Marking. Each service disconnecting means shall be marked with a sign(s). When located in a dedicated electrical room the exterior door(s) providing access to the disconnecting means located in a dedicated electrical room shall be permanently marked with a sign(s). Each sign shall be a minimum 1 sq. ft. (0.093 sq. m.), colored yellow with 1 inch (25.4 mm) high, ¼ inch (6.35 mm) stroke raised or engraved letters and/or numbers indicating the address or unit it serves and be identified as the "Electrical Service Disconnect(s)" and/or "Electrical Service Disconnect(s) Inside." Emergency Systems disconnects shall be permanently marked with sign(s), identified as "Emergency Electrical Disconnect(s)" and/or "Main Emergency Electrical Disconnect(s) Inside." When the service disconnecting means is located inside a dedicated electrical room and it is not the first service disconnect encountered or there are multiple service disconnects there shall be a directional 3 inch (75mm) wide painted yellow stripe on the floor from the entry door(s) to each service disconnect. Other durable means of identification may be used with prior approval by the Authority Having Jurisdiction (AHJ). Exception: One and two family dwelling units and their associated accessory structures. (3) Section 110.26. Spaces About Electrical Equipment. Amend by adding at the end of the sentence, the following: Required space at the panel(s) shall be defined by "painted lines" on the floor. The specified dimensions shall be held to the interior of the defined space, the painted line to the outside of the dimensions, and the width of the painted line shall be 6 inches. (4) Section 210.23. Permissible Loads, Multiple-Outlet Branch Circuits; Amend by adding to Subsection (A), to read as follows: (A) Dwelling unit: general lighting branch circuits in dwelling occupancies served by a fifteen ampere branch circuit shall not have more than twelve (12) power consuming outlets. A duplex receptacle is considered one (1) outlet. A small appliance branch circuit in dwelling occupancies served by a twenty ampere branch circuit shall have not more than eight (8) receptacle outlets." (5) Section 210.52. Dwelling Unit Receptacle Outlets, Subsection (A). Amend by adding the following paragraph to the end of that section: (A) General Provisions. "General lighting branch circuits in dwellings must not have more than 12 power consuming outlets. A duplex receptacle is considered to be one outlet. Smoke detectors are not considered to be power-consuming devices (for counting purposes.)" (6) Section 210.70. Lighting Outlets Required. Amend by adding to Subsection (2) Additional Locations: (4) Newly installed and/or renovated elevated deck areas, with access to ground level by stairway, shall have a light, on a switch or timer device, to illuminate said stairway. (7) Section 230.2. Number of Services. Amend by adding a new Subsection (F) entitled, "Individual Metering" to read as follows: (F) Individual Metering. Individual meters to measure electrical consumption shall be provided for each dwelling unit of a multifamily group when such dwelling units have separate heating and/or cooling systems whose primary energy source is electricity. (8) Section 230.79. Rating of Service Disconnecting Means, Subsection (C). (C) One-Family Dwellings. Amend by deleting the value of "one hundred (100) amperes" and substituting therefore the value of " two hundred (200) amperes" as the minimum service disconnecting means rating for single family dwellings. (9) Section 230.83. Emergency Disconnects, Residential. Amend by adding a new Section; For newly installed services, or heavy-ups of existing services, all shall have an emergency services disconnect in a readily accessible location on the exterior of the home. (10) Section 230.95. Ground Fault Protection of Equipment, Subsection (C). Amend by deleting the text in first paragraph and replacing it with the following text: (C) Performance Testing. "The ground-fault protection system shall be performance tested when first installed on site. The test shall be conducted by an approved independent testing company. A written record of this test shall be made available to the City of Gaithersburg prior to the final approval of the electrical systems." (11) Section 240.5. Protection of Flexible Cords, Flexible Cables, and Fixture Wires, Subsection B, Branch Circuit Overcurrent Device. Amend paragraph (4) as follows; (a) Extension cords shall not be used to hardwire a plug tail to equipment. Corded equipment must be rated for hard use and constructed using a rated assembly. (12) Section 250.52. Grounding Electrodes, Subsection (A), Paragraph (3). (3) Concrete-Encased Electrode. Amend by adding the following sentence at the end of the paragraph: "In cases where a metal underground waterpipe is not available, a concrete-encased electrode shall serve as the primary grounding electrode." (13) Section 250.62. Grounding Electrode Conductor Material. Amend by adding a new sentence at the end of the paragraph to read as follows: "The grounding electrode conductor shall be of copper for all one- and two-family dwellings." (14) Section 250.70. Methods of Grounding and Bonding Conductor Connection to Electrodes. Amend by adding new Paragraph (5) at the end of the paragraph to read as follows: (5) "In cases where a metal underground water pipe is not available, a concrete-encased electrode shall serve as the primary grounding electrode." (15) TABLE 311.12. Minimum Size of Conductors Section (A). Amend to read as follows: At the end of the text, add the statement: "Whether solid or stranded, conductors shall not be smaller than No. 14 copper. Whether solid or stranded, conductors shall not be smaller than No. 2 aluminum or aluminum alloy for commercial buildings only. Use of aluminum or aluminum alloy conductors in residential buildings is prohibited in branch circuits." (16) Section 410.1. Scope. Amend the paragraph to add the following after the last sentence of the paragraph: Commercial white box/vanilla shell installation or remodeling for future builds shall install permanent lighting fixtures. (17) Section 410.36. Means of Support Subsection (B) is deleted in its entirety and amended to read as follows: (B) Suspended Ceilings: All fixtures installed in suspended ceilings shall be supported directly from the building structure. A tie wire, minimum size No. 12 steel, from each (opposite) end of the fixture, secured to the building structure will suffice. Tie wire supports shall be installed vertically, or as close to vertical as possible. Exception. If the fixture is circular, and not more than 24" in diameter, at least one wire shall support the fixture as described above. (18) Section 440.62. Branch-Circuit Requirements Subsection (C). Amend to add the following statement at the end of the paragraph: (C) Where No Other Loads Are Supplied. "Each individual room air-conditioning unit regardless of its current rating, shall be served by an individual circuit of not less than No. 12 copper wire, and must terminate at a single receptacle." (19) Section 450.13. Accessibility. Is amended as follows: (B) Hollow Space Installations. Delete the section and replace with this sentence: "Hollow space installations of transformers shall not be permitted." Transformers shall not be installed above ceilings. Add new Subsection (C) as follows: (C) Support. Any transformer over 75KVA not mounted directly on the floor must have approved drawings detailing method of support. Submission shall include signed and sealed documents by a structural P.E., licensed in MD. (20) Section 625.15, Markings: Amend by adding a new Subsection (D) EV Labeling; EV label at the charger to be provided by the electrician "DANGER: DO NOT CHANGE SETTINGS. CONTACT QUALIFIED ELECTRICIAN". (21) Section 625.43, Disconnecting Means; Add the following at the end of the paragraph, "Provide an EV disconnect outside at the requisite charger or inside of the charger on all installations commercial and residential." (22) Section 700.18. Circuits for Emergency Power. Amend to add the following statements at the end of the paragraph: (a) "Any building requiring standpipes shall have installed one (1) 30 ampere, 120 volt circuit for each standpipe riser, supplied from the emergency panel. The wiring method for concealed work shall be conduit with appropriate metal boxes having gasketed flap door covers. The wiring method for concealed work shall be suitable for receiving the L5-20R NEMA type twist lock receptacle without damage." (b) "Supply wiring shall be at least 75 degrees C-type wire, one (1) single twenty (20) ampere three (3) wire twistlock receptacle (NEMA type L5-20R) shall be installed, at least as high as, and two (2) feet offset from each hose valve connection. Each outlet box shall be painted fire-alarm red in color and marked 'Only for Fire Department Use." (23) Section 760.41. NPLFA Circuit Wiring Paragraph (A): (A) Spread of Fire of Products of Combustion. Amend 2nd sentence by deleting the phrase "be permitted to" and replace with the phrase "shall be". Circuit shall be "locked on" to align with Chapter 11, the City of Gaithersburg Fire Safety Code.
(Ord. No. O-10-22, 10-3-22)
Ask a question about Gaithersburg law
Corpus searches the Gaithersburg sections it holds and shows the ones that match, with their citations. Free, no sign-in.