§ 5-913 — - Ventilation of restaurant type cooking equipment
Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 5-913
Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/73bc02fb-7a78-4210-ac3e-710e073eeddf
Sec. 5-913. - Ventilation of restaurant type cooking equipment.
The following provisions shall apply to ventilation of restaurant type cooking equipment: (1) Hoods over such equipment shall be constructed of noncombustible materials, with tight joints and have a clearance of at least 18 inches from all unprotected combustible materials. (2) Ducts from hoods over such equipment shall be constructed of No. 18 U.S. gauge or heavier steel, with tight joints and separated at least 18 inches from all unprotected combustible material. (3) The ducts shall constitute an independent system in no manner connected with any other ventilating system. (Ord. No. 81-65, § 8.8, 11-4-81)