§ 22-9-5 — Alternative emergency energy source options

2019 Detroit City Code (Supp. No. 4: codified through Ordinance No. 2024-17, effective March 26, 2024, and Ordinance No. 2024-32, effective June 25, 2024) · Detroit City Code § 22-9-5

Corpus is an independent public-information project, not the official City of Detroit website. Stable reference: corpuslaw.us/code/e79fff04-826c-451d-bf85-80ab8ea315b2

Sec. 22-9-5. - Alternative emergency energy source options.

(a) All senior housing facilities, as defined in Section 22-9-2 of this Code, shall have an alternative emergency energy source under this subsection or under Subsection (b) of this section. In accordance with the National Electrical Code 70, Article 700.12(A)—(E), which is contained the Michigan Electrical Code and is enforced by the City as provided for in Section 8-3-2 of this Code, an alternative emergency energy source shall include at least one of the following: (1) A storage battery shall be used as a source of power for emergency systems and shall be of suitable rating and capacity to supply and maintain the total load for a minimum period of one and a half hours: a. The storage battery may be alkali or acid type and shall be designed and constructed to meet the requirements of emergency service and shall be compatible with the charger for that particular installation as in accordance with NEC 70, Article 700.12(A); b. Automotive type batteries shall not be used; and c. An automatic battery charging means shall be provided by the senior housing facility; or (2) An uninterruptable power supply shall be used to provide power for emergency systems and shall comply with the applicable provisions of NEC 70, 700.12(A); or (3) A separate service shall be a service conductor sufficiently remote electrically and physically from any other service conductors to minimize the possibility of simultaneous interruption of supply, and shall be in accordance with the standards set forth in the Article 230 of the NEC; or (4) A fuel cell system used as a source of power for emergency systems shall be of suitable rating and capacity to supply and maintain the total load for not less than two hours of full demand operation: a. Installation of a fuel cell system shall meet the requirements of Parts II through VIII of Article 692 of the NEC; and b. Where a single fuel cell system serves as the normal supply for the building, it shall not serve as the sole source of power for the emergency standby system. (b) All senior housing facilities as defined in Section 22-9-2 of this Code, shall have an emergency generator in accordance with this subsection, or an alternative emergency energy source under Subsection (a) of this section: (1) The generator shall provide no less than four hours of service; (2) The generator shall generate enough power to provide lighting at all entrances and exits and to operate equipment to maintain fire detection, alarm, and extinguishing systems, telephone switchboards, heating and cooling plant controls, and other critical mechanical and medical equipment essential to the safety and welfare of the residents, personnel, and visitors; (3) The senior housing facility shall implement a monthly emergency generator system inspection, testing, and maintenance procedure: a. The generators are to be exercised for a minimum of 30 minutes each month in compliance with National Fire Protection Association, 110 (12) Section 7.9.2.4; b. A written record of generator inspections, tests, exercising, operation and repairs is to be maintained by the senior housing facility for three years and available for review upon request by a City official or employee. These records must also include: 1. The date of the testing and inspection; and 2. The name(s) and the credentials of the person(s) providing the service, identification of unsatisfactory conditions and corrective action taken, including parts replaced, and any testing of repairs recommended by the manufacturer; (4) The senior housing facility shall maintain an onsite fuel source to power emergency generators that will keep emergency power systems operational during the loss of electricity. The onsite fuel source shall be stored in compliance with state regulations; (5) The Buildings, Safety Engineering, and Environmental Department and the Detroit Fire Marshal or agent shall be present to witness the initial acceptance testing of the generator in accordance with National Fire Protection Association, 110.

(Ord. No. 15-19, § 1(26-9-4), eff. 3-1-2020)

Ask a question about Detroit law

Corpus searches the Detroit sections it holds and shows the ones that match, with their citations. Free, no sign-in.