Sec. 8-9-178. - Acceptance and periodic test of hydraulic cylinder and relief valve; test requirements.
(a) Hydraulic cylinders and relief valves shall be tested during the acceptance inspection and at least once every 30 months. The relief valve setting shall be in compliance with Section 3.19.4.2 of the ASME Code. (b) Where the relief valve setting is altered or the seal is broken, the relief valve shall be resealed. Hydraulic cylinders that are more than 35 years old shall be tested every 12 months. Each test shall be performed either by an unlimited-elevator contractor who is licensed by the City under Section 8-9-55 of this Code, or by an unlimited-elevator journeyperson who is licensed by the City under Section 8-9-75 of this Code. Unless requested by the designated inspector of the Department, by the holder of the Certificate of Registration as defined in Section 8-9-11 of this Code, or by the owner of the equipment a test conducted under this section need not be performed in the presence of a designated inspector of the Department. (c) Procedures for static load tests shall be as follows: (1) Put rated load in the car; (2) Locate the elevation of the platform with respect to a convenient reference and open the disconnect switch; and (3) For cylinders that are not completely exposed, after a minimum of 120 minutes, note the position of the platform with respect to the chosen reference. For cylinders that are completely exposed, after a minimum of 60 minutes, note the position of the platform with respect to the chosen reference. A change in the car position during a cylinder test that cannot be accounted for by visible oil leakage or temperature change of the oil indicates a failure of some type requiring further inspections, tests, or repairs. An accessible written record of all oil levels and all oil added shall be maintained in the machine room or control room. (d) The results of the test required under this section, including any defects found, shall be reported to the Department on a form furnished by the Department within 30 days of completion of the test. The report shall be signed by an unlimited-elevator journeyperson person who licensed by the City and is performing the test or under whose direct supervision the test is performed. The Department shall keep a record of all such tests. (e) It shall be unlawful for the holder of a Certificate of Registration as defined in Section 8-9-11 of this Code, or the owner of the equipment, to fail to have any test that is required to be performed under this section.
(Code 1964, § 5.3; Code 1984, § 5.3; Ord. No. 307-H, § 1(5.3), eff. 3-2-1979; Ord. No. 568-H, § 1(5.3), eff. 11-9-1983; Ord. No. 03-97, § 1(5.3), eff. 3-10-1997)
Ask a question about Detroit law
Corpus searches the Detroit sections it holds and shows the ones that match, with their citations. Free, no sign-in.