Sec. 8-2-14. - Fire hydrants.

(a) All required fire hydrants shall be positioned so the distance from the adjacent grade level is not less than 30 inches to the top of the hydrant and the large diameter outlet shall face the roadway and/or curb-line. (b) A fire hydrant is required to be positioned within 150 feet of a fire department connection for fire and life safety systems as approved by the fire code official.

(Ord. No. 4401, § 1, 2-19-2020)