§ 700.400 — Inspection And Maintenance
Code of Ordinances, City of O'Fallon, Missouri (Code 2026-10-22) · O'Fallon City Code § 700.400
Corpus is an independent public-information project, not the official City of O'Fallon website. Stable reference: corpuslaw.us/code/7083d26a-469e-499f-aae6-891f7c332dae
Section 700.400: Inspection And Maintenance.
A. Periodic inspection and testing schedules shall be established by the water supplier for all backflow prevention devices. Inspections will not exceed the following intervals. 1. Air-gap separations shall be inspected at the time of installation and every twelve (12) months thereafter. 2. Double-check valve assemblies shall be inspected and tested for tightness at the time of installation and at least every twelve (12) months thereafter. They shall be dismantled, inspected internally, cleaned, and repaired whenever needed and at least every thirty (30) months. 3. Reduced pressure principle backflow prevention devices shall be inspected and tested for tightness at the time of installation and at least every twelve (12) months thereafter. They shall be dismantled, inspected internally, cleaned, and repaired whenever needed and at least every five (5) years. B. All costs associated with inspections, testing, cleaning, repairs, overhaul or replacement of backflow prevention devices shall be the responsibility of the water customer. All inspections, testing, cleaning, repairs and overhauls of backflow prevention devices shall be performed by a State of Missouri Certified Backflow Prevention Service Tester. It shall be the responsibility of the customer to provide the City with written inspection documentation upon receipt. C. Backflow prevention devices found to be defective shall be repaired or replaced at the expense of the water customer without delay and in any event no later than thirty (30) days from the discovery of the defect. D. Backflow prevention devices shall not be bypassed, made inoperative, remove, or otherwise made ineffective without specific written authorization by the water supplier. Bypass piping around a backflow prevention assembly is allowed only if the bypass is equipped with an identical backflow prevention assembly. E. The water supplier shall maintain a complete record of each backflow prevention device. Records will include comprehensive listing of installation, tests, inspections, cleaning, repairs, and overhauls and generally be a complete history of each backflow prevention device from purchase to retirement. Records of customer repairs, cleaning, overhaul, and replacement shall be made available to the water supplier upon request.
[R.O. 2008 § 700.400; R.O. 2007 § 700.400; Ord. No. 1592 § 8, 5-17-1988 ; Ord. No. 3089 Art. I, 12-22-1993 ]
Ask a question about O'Fallon law
Corpus searches the O'Fallon sections it holds and shows the ones that match, with their citations. Free, no sign-in.