§ 6-235 — Emission limitations
Code of the City of Springfield, Missouri (Supp. No. 23, Update 2: codified through G.O. No. 6973, enacted January 12, 2026) · Springfield, Mo., City Code § 6-235
Corpus is an independent public-information project, not the official City of Springfield website. Stable reference: corpuslaw.us/code/11b32582-67bf-46d8-9c56-7f370e85ece3
Sec. 6-235. - Emission limitations.
(a) No person shall cause, allow or permit the emission of particulate matter from all the stacks of fuel burning equipment at a plant or on any premises in excess of 0.60 pound for each million BTU per hour total heat input if the total heat input of the equipment is 10,000,000 BTU or less. If the total heat input of the fuel burning equipment is more than 10,000,000 BTU, then the amount of particulate matter which may be emitted for each 1,000,000 BTU of total heat input shall decrease as the total heat input of the fuel burning equipment increases, as follows: (1) No more than 0.41 pound for each million BTU total heat input from equipment having a total heat input of 50,000,000; (2) No more than 0.35 pound for each million BTU total heat input from equipment having a total heat input of 100,000,000; (3) No more than 0.24 pound for each million BTU total heat input from equipment having a total heat input of 500,000,000; (4) No more than 0.21 pound for each million BTU total heat input from equipment having a total heat input of 1,000,000; (5) No more than 0.17 pound for each million BTU total heat input from equipment having a total heat input of 2,000,000; (6) No more than 0.14 pound for each million BTU total heat input from equipment having a total heat input of 5,000,000; (7) No more than 0.13 pound for each million BTU total heat input from equipment having a total heat input of 7,500,000; (8) No more than 0.12 pound for each million BTU total heat input from equipment having a total heat input of 10,000,000 or more. (b) The amount of particulate matter which may be emitted from fuel burning equipment having an intermediate total heat input between any of the total heat input amounts set forth in subsections (a)(1) through (8) of this section shall be determined either by linear interpolation, or by using the following equation: log Y = 0.2330 log X - 2.0111 where X represents each million BTU input of the total heat input and Y represents the allowable pounds of emissions.
(Code 1981, § 2A-15)
Ask a question about Springfield law
Corpus searches the Springfield sections it holds and shows the ones that match, with their citations. Free, no sign-in.