602. HEATING FACILITIES
602.1 Facilities required. Heating facilities shall be provided in structures as required by this section.
602.2 Residential occupancies. Dwellings shall be provided with heating facilities capable of maintaining a room temperature of 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms based on the winter outdoor design temperature for the locality indicated in Appendix D of the International Plumbing Code. Cooking appliances shall not be used to provide space heating to meet the requirements of this section.
Exception: In areas where the average monthly temperature is above 30°F (-1°C) a minimum temperature of 65°F (l8°C) shall be maintained.
602.3 Heat supply. Every owner and operator of any building who rents, leases or lets one or more dwelling units or sleeping units on terms, either expressed or implied, to furnish heat to the occupants thereof shall supply heat to maintain a temperature of not less than 68°F (20'C) in all habitable rooms, bathrooms, and toilet rooms.
Exceptions: 1. When the outdoor temperature is below the winter outdoor design temperature for the locality, maintenance of the minimum room temperature shall not be required provided that the heating system is operating at its full design capacity. The winter outdoor design temperature for the locality shall be as indicated in Appendix D of the International Plumbing Code. 2. In areas where the average monthly temperature is above 30°F (-1°C) a minimum temperature of 65 °F (l8°C) shall be maintained. 602.4 Occupiable workspaces. Indoor occupiable workspaces shall be supplied with heat to maintain a temperature of not less than 65°F (18°C) during the period the spaces are occupied.
Exceptions: 1. Processing, storage and operation areas that require cooling or special temperature conditions. 2. Areas in which persons are primarily engaged in vigorous physical activities.
602.5 Room temperature measurement. The required room temperatures shall be measured 3 feet (914 mm) above the floor near the center of the room and 2 feet (610 mm) inward from the center of each exterior wall.