§ 15-99 — Location of pipes
Code of Ordinances, City of Columbus, Mississippi (Supp. No. 15: codified through Amendment of October 21, 2025) · Columbus Code of Ordinances § 15-99
Corpus is an independent public-information project, not the official City of Columbus website. Stable reference: corpuslaw.us/code/adbf3151-e6b4-4058-b259-d801d63e3edc
Sec. 15-99. - Location of pipes.
Gas pipes shall have a lateral clearance of not less than four feet from water mains and 12 inches from any other subsurface structure; provided, that under exceptional circumstances, the gas inspector, with the written consent of the owner of the utility line involved, may authorize a lesser clearance. Pipes shall have a vertical clearance of 12 inches when crossing another pipe. Pipes shall be laid with a cover of not less than 30 inches except that under exceptional circumstances, the gas inspector may authorize less coverage. Where the trench is in rock, the cover may be 24 inches if the pipe is properly cushioned. In the event interference with other subsurface structures makes it impractical to maintain such depths, the gas inspector, with the written consent of the owner of the utility line involved, may permit gas pipelines and mains to be constructed so as to avoid such subsurface structures.
(Ord. of 5-6-69, § 2)
Ask a question about Columbus law
Corpus searches the Columbus sections it holds and shows the ones that match, with their citations. Free, no sign-in.