§ 4 — Local amendments to the 2023 National Electrical Code

Ocean Springs Selected Ordinances; partial (Adopted June 4, 2026; effective July 4, 2026) · Ocean Springs, Miss., Ord. No. 2026-012, § 4 · Effective

Corpus is an independent public-information project, not the official City of Ocean Springs website. Stable reference: corpuslaw.us/code/05aab670-eb4d-486a-8d2f-d677feca7100

SECTION 4.

LOCAL AMENDMENTS TO THE 2023 NATIONAL ELECTRICAL CODE. The following provisions of the 2023 National Electrical Code are hereby amended as follows:

A. Section 210.8 – Ground-Fault Circuit-Interrupter Protection for Personnel.

1. Section 210.8(A)(2) is amended to provide that GFCI protection shall not be required for receptacles installed in residential garage ceilings and utilized exclusively for garage door openers.

2. Section 210.8(A)(6) is amended to provide that GFCI protection for kitchen receptacles shall be required only where the receptacles are installed to serve countertop spaces or within 6 feet of a water source.

B. Section 210.8(D) – Specific Appliances Requiring GFCI Protection. GFCI protection shall not be required for:

(8) Electric ranges;

(9) Wall-mounted ranges;

(11) Clothes dryers; and

(12) Microwave ovens; unless specifically required by the manufacturer’s installation instructions to prevent damage to the appliance or to maintain warranty coverage.

C. Section 210.12 – Arc-Fault Circuit-Interrupter Protection. Arc-fault circuit-interrupter protection shall be required only for bedroom circuits and shall not be required in other rooms or spaces.

D. Table 210.24(1) – Copper Conductors. The use of 14 AWG copper conductors is prohibited. The minimum conductor size for feeders and branch circuits shall be 12 AWG copper.

E. Table 210.24(2) – Aluminum and Copper-Clad Aluminum Conductors. Aluminum and copper-clad aluminum conductors may be utilized only for service entrance conductors and feeders supplying distribution panels. Such conductors shall not be permitted for branch circuits.

F. 406.12 Tamper-Resistant Receptacles. Omitted in its entirety. Tamper-resistant receptacles shall not be required by the City of Ocean Springs.