§ 14.3.08 — Industrial And Commercial Wastes
Code of Ordinances, City of Starkville, Mississippi; partial · Starkville Code of Ordinances § 14.3.08
Corpus is an independent public-information project, not the official City of Starkville website. Stable reference: corpuslaw.us/code/b04e6e4f-ff6c-4b12-b406-9deb7a1e8dea
14.3.08 - Industrial And Commercial Wastes
Pretreatment. All industrial and commercial process wastewater shall be pretreated prior to discharge to the public sewers, if necessary, in accordance with the provisions of the United States Environmental Protection Agency, the Bureau of Pollution Control, and/or the city, whichever is more stringent. The minimum pretreatment requirements are as follows: Parameter | Maximum Concentration (mg/l BOD5 | 300.0* Suspended Solids (SS) | 300.0* TKN | 30.0* Arsenic | 0.05 Barium | 5.0 Boron | 1.0 Cadmium | 0.02 Chromium | 0.05 Copper | 0.02 Cyanide | 0.05 Lead | 0.10 Manganese | 0.50 Mercury | 0.002 Nickel | 0.08 Selenium | 0.02 Silver | 0.01 Zinc | 0.05 (*) BOD5, SS and TKN may be increased by written approval of the superintendent for limited periods of time. Permit requirements. As a condition for authorization to dispose of industrial wastes through the municipal system, the industrial applicant for a sewer permit shall provide the city with information describing wastewater constituents and characteristics, the type of activity and the quantity of production.
Ask a question about Starkville law
Corpus searches the Starkville sections it holds and shows the ones that match, with their citations. Free, no sign-in.