Sec. 23-175. - Moderate hazard.

(a) The activities set forth in this section are a moderate hazard and require the use of the specified backflow-prevention assembly. (b) An approved double-checkvalve assembly must be installed if the private water system is subject in any manner to pollution by any means as a result of the activities or processes associated with the use of the private water system. Following is a list of facilities, activities and processes which include, but are not limited to, conditions requiring the installation of an approved double-checkvalve assembly: (1) Nonresidential building or structure which is not a high hazard. (2) Distillery. (3) Fire sprinkler system or standpipe system without any of the following: chemical additive, booster pump or fire department connection (FDC). (4) Gas station. (5) Mobile home park. (6) Restaurant. (7) School. (8) Self-service laundry. (c) An approved double-checkvalve assembly must be installed in every private water system for which no other backflow-prevention assembly is otherwise specified.

(Code 1985, § 23-104; Ord. No. 2269, § 2, 3-24-2003; Ord. No. 5006, § 4, 11-26-2012)