Sec. 34-89. - Water supply—General.
(a) Required fire flow. Fire flow requirements for new occupancies and additions shall be determined by utilizing one of the following approved methods: (1) ISO — Guide for the Determination of Needed Fire Flow. (2) North Carolina Fire Code Appendix B. (b) Fire hydrants. Fire hydrant coverage shall not exceed the limits established in Chapter 5 and Appendix C of the North Carolina Fire Code to the most remote point of any building covered by the state fire code. The distance shall be measured along an approved path of travel for the fire apparatus. (c) Modification of distance requirements. Where warranted, the fire official shall have the authority to modify the distance requirements in subsection (b) based on the nature, construction and square footage of the occupancy.
(Ord. No. 14-117, § 1, 11-13-2014; Ord. No. 22-21, § 1, 3-10-2022)