§ 24.08.060 — Section 1201.4 Amended; PEX Tubing

Lincoln, Nebraska Municipal Code (enCodePlus online edition as published 2026-11-08 (history notes seen through Ord. 21775, Sept. 15, 2025)) · Lincoln Municipal Code § 24.08.060

Corpus is an independent public-information project, not the official City of Lincoln website. Stable reference: corpuslaw.us/code/c05479a1-e813-455f-8325-385943240d69

24.08.060 Section 1201.4 Amended; PEX Tubing.

Section 1201.4 of the Uniform Mechanical Code is amended to read as follows: Hydronic piping systems where the continuous pressure/temperature does not exceed the values in Table 1201.4 shall be permitted to be constructed of cross- linked polyethylene (PEX) tubing, subject to the construction and installation requirements set forth herein. TABLE 1201.4 PEX TUBING PRESSURE/TEMPERATURE TEMPERATURE (°F) | PRESSURE (psi) 73 | 160 180 | 100 200 | 80 For SI units: °C = (°F-32)/1.8, 1 pound-force per square inch = 6.8947 kPa

(Ord. 20527 §7, August 21, 2017)