§ 24.08.140 — Testing; General
Lincoln, Nebraska Municipal Code (enCodePlus online edition as published 2026-11-08 (history notes seen through Ord. 21775, Sept. 15, 2025)) · Lincoln Municipal Code § 24.08.140
Corpus is an independent public-information project, not the official City of Lincoln website. Stable reference: corpuslaw.us/code/f60a2d8d-6491-40d6-aae8-73a00a1aec8d
24.08.140 Testing; General.
General. Approved piping or tubing installed as a portion of a radiant panel system that will be embedded in the walls, floors, or ceilings of the building it is designed to heat shall be tested for leaks by the hydrostatic or air test method by applying not less than 50 psi above operating pressure. (689 kPa) water pressure or one and one-half times the operating pressure, whichever is greater.
(Ord. 20527 §13, August 21, 2017)
Ask a question about Lincoln law