25.06.501 Section 1109.2.5 Amended; Refrigerant Pipe Shafts.
Section 1109.2.5 of the International Mechanical Code is amended to read as follows: 1109.2.5 Refrigerant pipe shafts. Refrigerant piping that penetrates two or more floor/ceiling assemblies shall be enclosed in a fire-resistance-rated shaft enclosure. The fire resistance-rated shaft enclosure shall comply with Section 713 of the International Building Code. Exceptions: 1. Systems using R-718 refrigerant (water). 2. Piping in a direct system using Group A1 or A2L refrigerants. 3. Piping located on the exterior of the building where vented to the outdoors. ().