§ 49-828 — Reinforced concrete pipe
Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 49-828
Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/73fd53f7-ec24-44d8-ac32-020be0ed9e14
Sec. 49-828. - Reinforced concrete pipe.
The following provisions shall be observed regarding reinforced concrete pipe: (a) Circular pipe (RCP) with an inside diameter of 36 inches and smaller shall be Class III, Wall B or C pipe as defined by ASTM C76 Standard Specification for Reinforced Concrete Culvert, Storm Drain, and Sewer Pipe. (b) RCP with an inside diameter of larger than 36 inches shall be Class III, Wall B or C pipe as defined by ASTM C 655 Standard Specification for Reinforced Concrete Culvert, Storm Drain, and Sewer Pipe. (c) All pipe shall be stamped with the "Q" cast certification stamp. (d) Reinforced concrete pipe shall be used for storm sewers only.
(Ord. No. 40524, § 1, 10-20-15)