§ 54-116 — Rate-of-flow indicator
Omaha Municipal Code (Supp. No. 100, Update 2: codified through Ordinance No. 44760, enacted August 4, 2026) · Omaha Municipal Code § 54-116
Corpus is an independent public-information project, not the official City of Omaha website. Stable reference: corpuslaw.us/code/2cdfc0e4-2534-4061-93b6-7e3f541f09c2
Sec. 54-116. - Rate-of-flow indicator.
There shall be provided a rate-of-flow indicator on the pump discharge line leading to the filters which shall be calibrated for measuring both water for filtration and backwash. The activating element creating the pressure differential for indication of flow shall be installed with adequate clear distance upstream and downstream to obtain a reasonable degree of accuracy. The rate of flow indicators shall be installed in accordance with manufacturer's specifications. The rate-of-flow indicator shall be calibrated for and provided with a scale reading in gallons per minute and shall have a range of ten percent below the established filtration rate and ten percent above the backwash rate.
(Code 1980, § 54-116)
Ask a question about Omaha law