§ 33:5-49: SERVICE CHECK VALVES.
a. A proper check valve shall be placed in all water service connections where the following conditions exist: 1. Where a building is supplied by services connected to different sections of the mains. 2. Where there is any possibility of back-flow from tanks, siamese connections or other apparatus or fixtures within the building. b. Such check valves shall be installed on the outlet side of the meter setting, as near thereto as practicable, and clear of the meter by-pass connection, on meters two inches and larger. c. Check valves shall be of a type approved by the Division and shall be equipped with suitable auxiliary valves so as to permit periodic inspection of the check valve. d. Water supply lines to hot water boilers, steam boilers or similar fixtures or apparatus through which there might occur a back-flow of hot water or steam, shall be equipped with a suitable check valve, and with a relief valve installed between boiler or fixture or apparatus and the check valve.
[R.O. 1966 § 25:4-46]