§ 14-3-3-2 — MECHANICAL REQUIREMENTS
Albuquerque, New Mexico Code of Ordinances (2026 S-96: current through Ordinance 2026-033, passed 8-17-2026) · Albuquerque Code of Ordinances § 14-3-3-2
Corpus is an independent public-information project, not the official City of Albuquerque website. Stable reference: corpuslaw.us/code/9d441959-6afc-4ce3-9fdd-460d31e9ebae
§ 14-3-3-2 MECHANICAL REQUIREMENTS.
(A) Heating, Cooling, and Ventilation. (1) Heating and Cooling. (a) Every dwelling unit and guest room shall be provided with heating facilities capable of maintaining a room temperature of 68° F. at a point of three feet above the floor in all habitable rooms. Such facilities shall be installed and maintained in a safe condition and in accordance with the City’s currently adopted New Mexico Mechanical Code as adopted in the UAC. (b) Unvented fuel-burning heaters shall not be permitted. All heating devices or appliances shall be of an approved type. Ovens, stoves or ranges, or other cooking appliances shall not be used for the purpose of heating any portion of a dwelling. Approved portable space heaters may only be used as the sole source of heating on a temporary basis when the permanent heating system is being repaired or replaced. (c) Every dwelling unit shall be provided with cooling facilities. (i) Acceptable cooling facilities are fixtures that are permanently attached to the unit, including but not limited to: evaporative (“swamp”) coolers, central air conditioning, heat pumps, radiant cooling, window units, and mini-splits. (ii) Non-acceptable cooling facilities are temporary and/or portable devices such as fans, mobile evaporative coolers, and portable air conditioners, circulating devices such as ceiling fans, and ventilation systems and when used as the sole source of cooling for a unit, do not satisfy the requirements of this Section. These types of cooling facilities may only be used as a sole source of cooling on a temporary basis when the permanent acceptable cooling facility is being repaired or replaced. (2) Electrical Equipment. (a) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner in accordance with all applicable laws. All electrical equipment shall be of an approved type. (b) Every habitable room shall contain at least two supplied electric convenience outlets or one such convenience outlet and one supplied electric light fixture. Every toilet compartment, bathroom, laundry room, furnace room and public hallway shall contain at least one supplied electric light fixture. (3) Ventilation. Ventilation for rooms and areas and for fuel-burning appliances shall be provided as required in the Mechanical Code and in this code. Where mechanical ventilation is provided in lieu of the natural ventilation required by § 14-3-2-2(C), such mechanical ventilating system shall be maintained in operation during the occupancy of any building or portion thereof. ('74 Code, § 7-24-7) (Ord. 34-1986; Am. Ord. 2018-025; Am. Ord. 2024-047)
Ask a question about Albuquerque law
Corpus searches the Albuquerque sections it holds and shows the ones that match, with their citations. Free, no sign-in.