§ 54.05 — REQUIREMENTS FOR BACKFLOW PREVENTION

Municipal Code, City of Rio Rancho, New Mexico (Code 2026-04-23) · Rio Rancho Municipal Code § 54.05

Corpus is an independent public-information project, not the official City of Rio Rancho website. Stable reference: corpuslaw.us/code/b2b9adf9-78df-4156-bad3-decfff0f785f

§ 54.05: REQUIREMENTS FOR BACKFLOW PREVENTION.

(A) No water service connection to any residential or nonresidential premises shall be made by the city unless the water supply is protected as required or exempted by this chapter. Service of water to the premises may be discontinued or a notice of violation may be issued by the city to a customer if a backflow prevention assembly required by this chapter is not installed, tested, and maintained, or if it is found that a backflow prevention assembly has been removed, bypassed, or if an unprotected cross connection exists on the premises. (B) No water service connection to any residential property serviced by an auxiliary water supply shall be made by the city unless a backflow prevention assembly as required by this chapter protects the city’s water supply. Service of water to the residential premises with an auxiliary water connection may be discontinued if a backflow prevention assembly required by this chapter is not installed, tested, and maintained, or if it is found that a backflow prevention assembly has been removed, bypassed, or if an unprotected cross connection exists on the premises. (C) Water service to all premises containing possible health hazard potential cross connections will be discontinued and water service will not be restored until such conditions or defects are corrected. Customers with water service to premises with non-health hazard or pollution-related cross connections will be subjected to monetary penalties set forth in Section 51.12(H)(3) (R.O. 2003). (D) Based upon the degree of potential hazard, if the city determines that the premises of any customer requires a backflow prevention assembly on the water service connection to protect the city’s drinking water from actual or potential pollution and/or contamination hazard, then the customer shall install an approved assembly at the customer’s own expense. Failure, refusal or inability on the part of the customer to install, have tested, and maintain said assembly(s) shall constitute a violation and may be grounds for discontinuing water service to the premises until such requirements have been satisfactorily met. (1) The customer shall have the assembly tested by a certified backflow prevention assembly tester or repairman. Upon completion of installation, the customer shall notify the Utilities Division. All assemblies must be tested by a certified backflow tester/repairman within 14 days after installation. The newly installed backflow prevention assembly shall be inspected by the city. (2) The customer shall, at the customer’s expense, have the backflow prevention assembly tested annually by a certified backflow prevention assembly repairman and/or tester and the customer shall have the certified backflow prevention assembly repairman correct any malfunction of the backflow prevention device which is revealed by testing. (3) The customer shall, at the customer’s expense, register all backflow prevention assemblies with the city and shall provide the date of installation, name of manufacturer, model, type, size, serial number of the backflow prevention assembly, and a copy of the initial test report to the Utilities Division. (4) The customer must protect the backflow prevention assembly from freezing and other severe weather conditions. (5) When the assembly has been registered with the city and inspected by the city, the Utilities Division shall permit the water service in accordance with the provisions of this chapter. Noncompliance constitutes a violation of the chapter and is grounds for enforcement action as listed in Section 54.11 and water service to the premises may be denied. (6) The customer shall, at the customer’s expense, be responsible for all applicable fees or costs related to the testing, retesting in the case that the device fails to operate correctly, repair and replacement of faulty assemblies. The customer shall notify the Utilities Division in advance when the tests are to be undertaken so that a city representative may witness the field tests if so desired. Records of such tests, repairs and overhauls shall be kept by the customer and these records made available to the Utilities Division. (E) Inspection and entry. (1) The customer shall allow the city, or an authorized representative, upon presentation of proper credentials, to enter at reasonable times upon or through the premises to conduct a survey, inspection or investigation of a backflow prevention assembly and records on the premises. In the event that the inspection or investigation determines that a contamination hazard may exist, the Utilities Division shall immediately terminate water service to the premises. Water service shall be restored to the premises once the contamination hazard has been controlled or eliminated, the premises are inspected, and any backflow prevention assemblies required by the Utilities Division have been installed and tested by a certified backflow prevention repairman or tester, and the test results are received by the Utilities Division. (2) In the event no contamination hazard or substantial dangers are determined to exist, but actual or potential cross connections require control by containment, notice shall be given in writing to the customer by the Utilities Division to install an approved reduced pressure principle backflow prevention assembly within 60 days. The customer will correct the conditions(s) in conformance with Title 14, Chapter 8, Part 14.8.2.15 of the Construction Industries Divisions Rules, New Mexico Administrative Code relating to water supply and distribution and the regulations adopted pursuant thereto. (F) When required by the city, the customer shall have installed an approved backflow prevention assembly at or near the property line or immediately inside the building being served, but in all cases, before the first branch water line leading off the service line. (G) The type of protective assembly required is as follows: (1) When required by the city, nonresidential customers with water connections, except for irrigation systems, must install an approved reduced pressure principle backflow prevention assembly at each service connection to the customer’s water systems. (2) All connections, including residential, where there is an auxiliary water supply shall have no direct or indirect cross connections with potable water systems, unless an approved air gap or an approved reduced pressure principle backflow prevention assembly shall protect the public water system. (3) The customer responsible for the irrigation water systems connected to the public water system must install an approved pressure vacuum breaker, approved spill-resistant pressure vacuum breaker or an approved reduced pressure principle backflow prevention assembly at the potable service connection. (4) Reclaimed wastewater systems. (a) Reclaimed wastewater systems shall have no direct or indirect cross connections with potable water systems pursuant to the latest revision of the New Mexico Plumbing and Mechanical Code. All piping, valves and outlets shall be colorcoded in purple to differentiate piping or fixtures used to convey reclaimed wastewater from piping or fixtures used for potable or other water. Those portions of reclaimed wastewater systems that are underground and were installed prior to the adoption of the state policy are exempt from the purple color-coding requirement if all accessible portions of the reclaimed wastewater system are colored purple or clearly labeled as being part of a reclaimed wastewater distribution system. (b) In cases where parts of a public and private irrigation system are being upgraded and any of the abandoned potable water line is being transferred to the reclaimed water/nonpotable system, a physical break must be made at the service connection. As each section is completed, the new system shall be shut down and drained and each water user checked to ensure that there are no improper connections. For reclaimed wastewater systems that were installed prior to the adoption of the state policy, the absence of cross connections may be demonstrated via hydrostatic testing or asbuilt drawings, supported by an affidavit under oath that no cross connection exists. (5) All new fire protection systems, including fire line services to residential fire protection systems, shall be equipped with an approved reduced pressure principle backflow prevention assembly installed at each service connection. (6) All fire hydrants used for drawing water for filling tanks and tank trucks and for temporary irrigation systems must have an approved reduced pressure principle backflow prevention assembly or air gap. (H) The customer shall be responsible for the elimination or control of all cross connections on his premises. The customer shall not install a bypass around any backflow prevention assembly unless there is a backflow prevention assembly of the same type on the bypass. Customers who cannot shut down their operation for testing of the device(s) must supply additional assemblies as necessary to allow testing to take place. (I) The customer is responsible to eliminate the possibility of thermal expansion, if a closed system has been created by the installation of a backflow prevention assembly. (J) Any increase or reduction in water pressure caused by the installation of a backflow assembly is not the responsibility of the city. (K) Any existing backflow prevention assemblies installed on water connections for nonresidential premises prior to November 1, 2006 (with the exception of fire protection systems and irrigation connections) that are not on the current list of approved backflow prevention assemblies may be approved to continue in service provided the assemblies serve as adequate protection for the potential hazards and provided that the assemblies can be maintained, tested, and that repair parts are available through the manufacturer. Whenever obsolete backflow prevention assemblies are replaced, they shall be replaced with current approved backflow prevention assemblies. (L) (1) All customers who hold a city business license and whose premises do not contain backflow prevention assemblies are subject to inspection by the Utilities Division to determine if a cross connection with a contamination or pollution hazard exists, or may potentially exist. Based on the possible degree of hazard, the customer may be required to install an approved backflow prevention device at the premises. (2) Buildings and facilities that may introduce harmful substances to a public water system include, but are not limited to: Hospitals, morgues, mortuaries, medical clinics, dental clinics, and autopsy facilities. Laboratories and all types of research facilities. Sewage treatment plants or facilities. Food and beverage processing plants. Chemical plants. Petroleum refineries. Metal plating industries. Electric and electronic component manufacturers. Radioactive material processing plants. Car and truck wash facilities. Hydraulic testing facilities. Packing houses, rendering plants, tanneries, and stock yard facilities. Steam generating facilities. Laundries, dry cleaners, and laundromats. Photographic film processing facilities. Swimming pools and health spas. Greenhouses. Multistory buildings in excess of 30 feet. Taxidermy shops. Battery shops. Kennels, pet stores, and zoos. Printing shops and screen printing shops. Jewelry manufacturers. Radiator shops. Warehouses. Sand and gravel facilities. Power plants. Breweries. Restaurants. Veterinary offices. Hotels and motels. Schools and colleges. Golf courses. Recycled water systems. Salons. (3) After July 1, 2011, the customer shall notify the Utilities Division within 30 days when: (a) The premises is sold or leased; (b) The premises is remodeled and such work requires a building permit; (c) The type of business conducted at the premises changes. (M) Any existing fire protection systems installed prior to November 1, 2006, containing double check valve backflow prevention assemblies are approved to continue in service. If the existing fire protection system is modified, replaced, extended or added on to, the customer shall replace the existing double check valve assembly with an approved reduced pressure principle backflow prevention assembly at or near the service connection. (N) All backflow prevention assemblies for nonresidential irrigation connections shall either be that of a reduced pressure principle backflow prevention assembly, a pressure vacuum breaker or spill-resistant pressure vacuum breaker. A pressure vacuum breaker or spill-resistant pressure vacuum breaker must not be subjected to backpressure. Any existing atmospheric vacuum breakers used for containment purposes at nonresidential irrigation connections shall be preceded with any of the approved listed assemblies. (O) Approved backflow prevention assembly. (1) Any backflow prevention assembly required herein shall be a make, model and size approved by the city. “Approved backflow prevention assembly” shall mean an assembly that has been manufactured in conformance with the standards established by the American Water Works Association listed in the recent edition of the Uniform Plumbing Code entitled: (a) AWWA/ANSI C511-97 Standard for Reduced Pressure Principle Backflow Prevention Assemblies; (b) AWWA/ANSI C510-97 Standard for Double Check Valve Backflow Prevention Assemblies. (2) In addition, approved backflow prevention assemblies have met the laboratory and field performance specifications of the Foundation for Cross-Connection Control and Hydraulic Research of the University of Southern California (USC FCCCHR) Specification of Backflow Prevention Assemblies – Section 10 of the most current edition of the Manual of Cross-Connection Control. (3) Said AWWA and USC FCCCHR standards and specifications have been adopted by the city. Final approval shall be evidenced by a Certificate of Compliance for the said AWWA standards; or Certificate of Approval for the said USC FCCHR Specifications; issued by an approved testing laboratory. (4) The following testing laboratory has been approved by the city to test and approve backflow prevention assemblies: Foundation for Cross-Connection Control and Hydraulic Research University of Southern California KAP-200 University Park MC-2531 Los Angeles, California 90089-2531 (5) Testing laboratories other than the laboratory listed above may be added to the approved list. (P) The city is authorized to make all necessary and reasonable rules and policies with respect to the enforcement of this chapter. All such rules and policies shall be consistent with the provisions of this chapter.

( Ord. 06-64 ; Am. Ord. 11-10 )

Ask a question about Rio Rancho law

Corpus searches the Rio Rancho sections it holds and shows the ones that match, with their citations. Free, no sign-in.