§ 26-204 — Requirements
Code of Ordinances of the City of Roswell, New Mexico (Codified through Ordinance No. 24-19, adopted November 14, 2024. (Supp. No. 16)) · Roswell Code of Ordinances § 26-204
Corpus is an independent public-information project, not the official City of Roswell website. Stable reference: corpuslaw.us/code/50f5f041-71ad-4a4b-9347-77225153efed
Sec. 26-204. - Requirements.
Mandatory cross connection control by containment: (1) Effective January 1, 2025 all new non-residential premises shall have a containment reduced pressure principle backflow prevention assembly approved by the city installed after the domestic service connection, as set forth in the UPC and this article. No tees, branches or possible connection fittings or openings will be allowed between the containment backflow prevention assembly and the service connection unless protected by a backflow prevention assembly. (2) Effective January 1, 2034 all existing non-residential premises shall have a containment reduced pressure principle backflow prevention assembly approved by the city installed after the domestic service connection, as set forth in the UPC and this article. No tees, branches or possible connection fittings or openings will be allowed between the containment backflow prevention assembly and the service connection unless protected by a backflow prevention assembly. A backflow prevention assembly maybe required immediately if it is determined there is a high hazard or likelihood of contamination of the public water system. (3) Effective January 1, 2024 all remodeled non-residential premises, when the work area of the building undergoing repairs, alterations or rehabilitation, as defined in the International Existing Building Code, exceeds 50 percent of the aggregate area of the building regardless of the costs of repairs, alteration, or rehabilitation, shall have a containment reduced pressure principle backflow prevention assembly approved by the city installed after the domestic service connection, as set forth in the UPC and this article. No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection unless protected by a backflow prevention assembly. (4) All construction premises with temporary service connection shall have a containment reduced pressure principle backflow prevention assembly approved by the city installed at each temporary service connection to the construction site, as set forth in the UPC and this article. (5) All non-residential irrigation water systems connected to the public water system shall have a pressure vacuum breaker, spill-resistant pressure vacuum breaker or a reduced pressure principle backflow prevention assembly installed after the service connection. Such devices shall be approved by the city. No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection. (6) All non-residential customers connected via piping to an alternative water source or an auxiliary water supply and the public water system shall install a containment reduced pressure principle backflow prevention assembly approved by the city after the potable service connection. (7) Effective January 1, 2024 new ¾" and 1" service lines will be installed with a check valve incorporated into the meter box. (8) Effective January 1, 2024 all new and replacement water heaters will require a thermal expansion tank to be installed. (9) Effective January 1, 2034 all residential connections shall have backflow prevention at either the meter box or at the service entrance into the residence. (10) All residential irrigation water systems connected to the public water system shall have a pressure vacuum breaker, spill-resistant pressure vacuum breaker or a reduced pressure principle backflow prevention assembly installed after the service connection. Such devices shall be approved by the city. No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection. (11) Any residential premises having existing private wells and who desire to connect to the public water system shall have two options as follows: a. Customers shall permanently abandon the use of private wells by plugging the wells as accepted by the city prior to connecting to the public water system; or customers who choose to maintain their private wells shall install a containment reduced pressure principle backflow prevention assembly approved by the city. The assembly shall be installed immediately after the water meter on the customers service line. b. All fire hydrants used for drawing water for filling tanks and tank trucks and for temporary irrigation systems must use a hydrant meter with backflow prevention provided by the city. (12) Effective January 1, 2024, all new services to private fire protection systems shall be equipped with a containment reduced pressure principal backflow prevention assembly approved by the city and fire marshal having jurisdiction installed after the service connection. No tees, branches or possible connection fittings or openings are allowed between the containment backflow prevention assembly and the service connection. A double check valve assembly approved by the city and fire marshal having jurisdiction may be installed instead of a reduced pressure backflow prevention assembly provided the private fire protection system meets or exceed ANSI/NSF Standard 60 61 throughout the entire private fire protection system, the fire sprinkler drain discharges into atmosphere, and there are no reservoirs, fire department connections nor- connections from auxiliary water supplies. (13) Premises with existing private fire protection systems containing double check valve assemblies installed and approved by the city prior to 2024 are approved to continue in service as long as the device tests and functions properly. (14) Effective January 1, 2025 all remodeled non-residential premises, when the work area of the building undergoing repairs, alterations or rehabilitation, as defined in the International Existing Building Code, exceeds 50 percent of the aggregate area of the building regardless of the costs of repairs, alteration, or rehabilitation with existing private fire protection systems without a containment backflow prevention assemblies shall be retrofitted with an approved reduced pressure principle backflow prevention assembly approved by the city and fire marshal having jurisdiction. Assembly shall be installed at each private fire protection after the service connection to the customers water system. Approved reduced pressure principle backflow prevention assembly shall be installed by a person who is licensed by the appropriate mechanical classification in accordance with the New Mexico Construction Industries Licensing Act. Fire sprinkler system hydraulic performance shall be verified by an engineer registered in accordance with the State of New Mexico Board of Licensure for Professional Engineers and Surveyors, pursuant to the Engineering and Surveying Practice Act, NMSA 1978 §§ 61- 23-1 through 61-23-32. (15) Once an approved backflow prevention assembly is installed at a premises, as a cross connection control containment assembly, the assembly shall not be removed without prior approval from the city. Containment backflow prevention assemblies that cannot be repaired must be replaced in-kind per the terms of this article. (16) Once an approved backflow prevention assembly for containment has been properly installed the assembly shall not be modified. (17) Inspection of premises. a. Right of entry. Whenever necessary to make an inspection to enforce any of the provisions of this article, or whenever the city or its authorized representative has reasonable cause to believe that there exists in any building or upon any premises, any condition which may endanger the public water supply, the city or its authorized representative may enter such building or premises at reasonable times to inspect the same or to perform any duty imposed upon the city by this article; provided that if such building or premises be occupied, the city representative will first present proper credentials and demand entry; and if such building or premises be unoccupied, the city representative will first make a reasonable effort to locate the owner or other persons having charge or control of the building or premises and demand entry. If entry and or inspection is refused, the city may immediately terminate water service to the premises. b. Inspection of premises. The purpose and authority to conduct such an inspection shall be disclosed to the customer. If actual or potential cross connections, which could result in backflow of contaminants, pollutants, water from auxiliary water supplies or water from non-potable water systems are determined to exist during the premises inspection, the city shall proceed as follows: 1. In the event contamination of the public water supply is determined to exist, the city shall immediately terminate water service to the premises. The city shall restore water service to the premises once the contamination hazard has been controlled or eliminated. 2. In the event no contamination is determined to exist, but actual or potential cross connections require control by containment, the city shall give the customer written notice to install an approved backflow prevention assembly as a cross connection control containment assembly after the service connection at the customer's own expense. The backflow assembly shall be installed, inspected and tested within 15 calendar days from the date of the notice. For good cause, the city may extend the time to comply with the requirements of this article. c. Re-inspection. Re-inspection of premises shall be conducted by the city to verify corrective action has been implemented as required by this article. (18) Installation of backflow prevention assemblies. Any contractor licensed by the appropriate mechanical classification in accordance with the New Mexico Construction Industries Licensing Act may install backflow prevention assemblies in accordance with the UPC and this article. The contractor shall be responsible for obtaining all required approvals, such as approved plans, permits and inspections. Such contractor shall not change the design, material or operational characteristics of a backflow prevention assembly without prior approval of the city. (19) Tests and maintenance of backflow prevention assemblies. Customers shall have their existing containment and isolation backflow prevention assemblies tested at least once a year by a certified backflow prevention assembly tester. Assemblies that fail a test shall be repaired or replaced by a certified backflow prevention assembly repairman and immediately retested by a certified backflow prevention assembly tester. A test report shall be submitted to the customer and the city within seven calendar days of test, or the test will be void, and retesting will be required. Tests and repairs shall be at the expense of the customer. (20) All new installations of backflow prevention assemblies shall be tested immediately upon installation (if/when water service is available) and test reports submitted to the city within seven calendar days or the tests will become void and retesting would be required. Once the backflow prevention assembly is tested and operating properly, water service to the premises may continue. The city shall inspect all newly installed containment backflow prevention assemblies. (21) The repairman and tester shall use separate tools and gauges for testing backflow prevention assemblies on potable water systems, such tools and gauges are never to be used on non-potable water, including alternate water sources. They shall submit all test reports to the city and customer with seven calendar days of the test, or the test becomes void, and retesting of assembly would be required. The city shall provide the test report form to customers, certified backflow prevention assembly testers, and repairmen upon request. They shall submit test gauge calibration test report annually to the cross connection manager. Tests performed with a test gauge that has not had a yearly calibration certification are void. Accurate records of all inspections, tests, repairs, and replacement of backflow prevention assemblies shall be maintained by the customer for a period of three years. (22) Existing previously approved backflow prevention assemblies. Any existing backflow prevention assemblies that were previously approved may be approved to continue in service provided that the assemblies test and function properly. When required, obsolete assemblies shall be replaced with current, approved backflow prevention assemblies. (23) Certification of testers and repairmen. To be certified as a backflow prevention assembly tester, a person shall attend a training course that has been approved by the city and successfully complete the written and practical examinations administered as part of the approved training course. A person who is licensed by the appropriate mechanical classification in accordance with the New Mexico Construction Industries Licensing Act and attends and successfully completes the approved training course may be certified as a backflow prevention assembly repairman. (24) Re-certification of testers and repairmen. A certified tester or repairman who wishes to remain active as a backflow assembly tester or repairman shall renew their certification every three years. To re-certify, prior to existing certification expiring, testers and repairmen must complete an approved eight-hour training course and accrue 16 hours of approved continuing education credits. Otherwise, the certified tester or repairman must complete an approved forty-hour training course. Testers or repairmen with non-expired certifications shall provide proof of training credits earned and training course attended prior to re-certification. (25) Approved training courses. The city shall approve training courses. The approved course shall be conducted by an instructor who is a certified tester and repairman; duration of the course shall be at least 40 hours; and the minimum material covered shall either be based on the University of Southern California's Foundation for Cross Connection Control and Hydraulic Research training course or an ANSI accredited listing agency. (26) The approved re-certification training course shall be conducted by an instructor who is a certified tester and repairman; duration of the course shall be at least eight hours and the course shall include rules, regulations, the cross connection article, practical training and practical examinations. (27) The instructor conducting the certification and re-certification courses shall administer the written and practical examinations. A performance of over 70 percent on the written examination and satisfactory completion of the practical examination constitutes successful completion of the course. (28) Administrator of the approved training course or approved recertification training course shall submit the course syllabus once a year, or upon any changes to the syllabus for approval by the city.
(Ord. No. 24-05, § 2, 4-11-2024)
Ask a question about Roswell law
Corpus searches the Roswell sections it holds and shows the ones that match, with their citations. Free, no sign-in.
Use the Roswell code through the API
This call searches the Roswell code. Change jurisdiction to the state's code to search its statutes and its cities, or to US for federal law. A free key gives 1,000 searches a month, and the MCP server works with no key.
curl -H "Authorization: Bearer $CORPUS_API_KEY" \
"https://corpuslaw.us/api/v1/search?q=Requirements&jurisdiction=NM-ROSWELL"Law search API · Docs · Get a free key · Connect the MCP server