§ 66-18: Stokers.
A. No spreader stoker shall be installed or used in connection with any fuel-burning plant, equipment or device unless properly equipped with a fly-ash eliminator and steam or air jets approved by the Chief Combustion Inspector. B. No person shall install, operate or use any stoker in connection with any fuel-burning plant, equipment or device unless the following listed stoker settings are maintained: Required Stoker Settings (cast-iron and steel boiler-stoker setting heights; minimum required distance from lowest point of crown sheet to top of stoker retort) For Stokers Feeding Not Over(pounds per hour) | Distance(inches) 30 | 20 40 | 22 50 | 24 75 | 26 100 | 28 150 | 30 200 | 32 300 | 34 400 | 36 500 | 39 750 | 46 1/2 1,000 | 54 C. For cast-iron boilers, seven-eighths (7/8) of the minimum headroom specified may be used. Water grate tubes in boilers so equipped must be removed in making stoker installations.
[Amended 12-9-2003 , effective 12-19-2003 ]