§ 94-28 — Determination of boiler horsepower
Code of Ordinances of the City of Buffalo, New York (Code 2026-03-31: eCode360 publication current through the 2026-03-31 codification (imported 2026-11-12)) · Buffalo City Code § 94-28
Corpus is an independent public-information project, not the official City of Buffalo website. Stable reference: corpuslaw.us/code/51d6008b-a9e7-4514-b35f-347b5b669b13
§ 94-28: Determination of boiler horsepower.
A. The rated boiler horsepower as used in this chapter shall be determined by: (1) For any boiler or steam generator, the maximum rated steam-generating capacity per hour for heating water from and at 212° F., divided by 34 1/2. (2) For water or fire-tube boilers having a drum or drums 18 inches or larger, the rated water-heating surface divided by 10, or for any other steam generator or boiler, the rated water-heating surface divided by five. (3) For hot-water or steam boilers, the rated British thermal unit heat transfer to the water-heating surface per hour, divided by 33,475. B. The conditions above described resulting in the maximum boiler horsepower rating shall apply, and the determination of the Chief Combustion Inspector shall govern the horsepower rating of such steam generator or boiler.
Ask a question about Buffalo law