§ 131-229 — Ventilation
Code of the City of Mount Vernon, New York · Mount Vernon City Code § 131-229
Corpus is an independent public-information project, not the official City of Mount Vernon website. Stable reference: corpuslaw.us/code/c32ab677-3701-4063-bb26-1af536a19e03
§ 131-229: Ventilation.
A. Ovens in which flammable or toxic vapors are liberated or through which products of combustion are circulated shall be ventilated by the introduction of a supply of fresh air and proper exhaust to outdoors. Such oven ventilation shall be arranged to provide vigorous and well distributed air circulation within the oven and to ensure that the flammable vapor concentration will be safely below the lower explosive limit at all times. Unless the oven is operated in accordance with specific approval specifying particular solvents and rate of ventilation, the rate of ventilation shall not be less than 10,000 cubic feet of fresh air per gallon of solvent evaporated in continuous-process ovens, and not less than 380 cubic feet per minute per gallon of flammable solvent evaporated in batch-process ovens. B. Exhaust duct openings shall be located in the area of greatest concentration of vapors. C. All exhaust shall be by mechanical means using power-driven fans.