BC 1509 — Radiant Barriers Installed above Deck
New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Building Code § BC 1509
Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/d23dcc62-ddeb-47a9-bbcf-23cf7360eb58
Section BC 1509: Radiant Barriers Installed above Deck
1509.1 General. A radiant barrier installed above a deck shall comply with Sections 1509.2 through 1509.4. 1509.2 Fire testing. Radiant barriers shall be permitted for use above decks where the radiant barrier is covered with an approved roof covering and the system consisting of the radiant barrier and the roof covering complies with the requirements of either FM 4550 or UL 1256. 1509.3 Installation. The low emittance surface of the radiant barrier shall face the continuous airspace between the radiant barrier and the roof covering. 1509.4 Material standards. A radiant barrier installed above a deck shall comply with ASTM C 1313/1313M.