§ 210.11

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 210.11

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/e877b66b-1484-4018-ad73-3378d6597bdd

Section 210.11

Section 210.11 (C)(4) – Add a new Informational Note to Section 210.11(C)(4) to read as follows: Informational Note: See Residential Provision of the New York City Energy Conservation Code, for additional Electrical Vehicle (EV) requirements. Section 210.11(C)(5) – Add a new Section 210.11(C)(5) to read as follows: (5) Air-Conditioning Branch Circuit. In addition to the number of branch circuits required by other parts of this section, an individual branch circuit shall be provided for each air-conditioning receptacle outlet required by 210.52(J).