§ 230.44

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 230.44

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/e8dddf03-ce50-4537-a2af-0015a41ab6c8

Section 230.44

Section 230.44 – Revise Section 230.44 to read as follows: 230.44 Cable trays. Cable tray systems shall be permitted to support service-entrance conductors. Cable trays used to support service-entrance conductors shall contain only service-entrance conductors listed for use in cable trays and shall be limited to Type MI Cable. Such cable trays shall be identified with permanently affixed labels with the wording “Service-Entrance Conductors.” The labels shall be located so as to be visible after installation with a spacing not to exceed 10 ft (3 m) so that the service-entrance conductors are able to be readily traced through the entire length of the cable tray.