§ 250.119

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 250.119

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/f1f17b4e-4f1d-4a6c-95c7-672512ca608f

Section 250.119

Section 250.119 – Revise the Exception No. 1 in Section 250.119 to read as follows: Exception No. 1: Power-limited Class 2 or Class 3 cables, or communications cables containing only circuits operating at less than 50 volts ac or 60 volts dc where connected to equipment not required to be grounded shall be permitted to use a conductor with green insulation or green with 1 or more yellow stripes for other than equipment grounding purposes.