§ 27-364 — Exit discharge

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Admin. Code § 27-364

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/301026a4-9ea3-43b0-b3be-b9904a56d47d

§ 27-364 Exit discharge.

All vertical exits shall extend in a continuous enclosure to discharge directly, or by way of a yard, court, or exit passageway, to an open exterior space. When vertical exits serving floors above grade continue in the same enclosure to serve floors below grade, the portion of such vertical exits above grade shall be separated from the portion below grade by construction having at least a one hour fire-resistance rating, with three-quarter hour self-closing doors opening in the direction of exit travel from the floors below grade, except that buildings classified in residential occupancy group J-3 and educational occupancy group G shall be exempt from this requirement.