§ 27-870 — Chimney connector construction

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Admin. Code § 27-870

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/a403d460-0e79-4f16-be7c-3b3dee9d1131

§ 27-870 Chimney connector construction.

Chimney connectors except those serving incinerators shall be constructed of galvanized steel of thickness conforming to the requirements listed in subdivision (a) of this section or of equivalent materials. Cleanout doors of the same material as the connector or other equivalent means shall be provided for the cleaning of connectors. Tile pipe shall not be used as a chimney connector. (a) Thickness of metal. The thickness of galvanized steel for chimney connectors shall be not less than that given in table 15-7. TABLE 15-7 Required Thickness of Galvanized Steel for Connectors Galvanized Sheet Gauge No. Area of Connector Sq. In. 24 less than 79 22 80 to 154 20 155 to 200 16 Over 200 (b) General. All chimney connectors shall be as short and as straight as possible consistent with their use and the required draft conditions. No chimney connector shall pass through a floor or ceiling construction.