FC 3510 — Hot Work on Flammable and Combustible Liquid Storage Tanks
New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Fire Code § FC 3510
Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/3cae50d6-b6cd-438d-81be-24439e1b33b6
Section FC 3510: Hot Work on Flammable and Combustible Liquid Storage Tanks
3510.1 General. Hot work performed on the interior or exterior of tanks that hold or have held flammable or combustible liquids, when approved, shall be conducted in accordance with this section and NFPA 326. 3510.2 Department approval. Approval shall be obtained from the department prior to conducting hot work on a tank that holds or has held flammable or combustible liquids. The application shall justify the need to conduct such hot work and identify the potential hazards and methods of controlling such hazards. 3510.3 Hazard prevention. A pre-hot work check shall be performed in accordance with FC 3504.3.1. A fire watch shall be maintained with a combustible gas detector, to continuously monitor the work area and any other affected areas. 3510.4 Hot tapping. Hot tapping may be conducted at bulk plants and terminals on tanks and piping only when approved by the department. Such work shall be conducted by persons with approved qualifications.
Ask a question about New York law