§ 352.10

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 352.10

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/b89efa33-80ad-46dd-9871-e2124489ae56

Section 352.10

Section 352.10 – Add new Sections 352.10(J) and 352.10(K) to read as follows: (J) Buildings Not Exceeding 3 Stories. In any building or dwelling unit not exceeding 3 stories above grade. (K) Buildings Exceeding 3 Stories. Unless prohibited elsewhere by other articles of this code; in any building exceeding 3 stories above grade where the PVC conduit is concealed within non-plenum walls, floors, or ceilings constructed with materials providing a listed 1-hour fire rated assembly or PVC conduit encased in concrete, minimum 2 inches (50.8 mm) thick.